Tehnika
2016, vol. 71, iss. 2, pp. 263-269
article language: Serbian
document type: Professional Paper
published on: 27/04/2016
doi: 10.5937/tehnika1602263K
Creative Commons License 4.0
Construction of turbogenerator capability curve for high reactive power region by Potir reactance
University of Belgrade, Electrical Engineering Institute 'Nikola Tesla'

Abstract

Calculation and analysis potier reactance dependence in high reactive power region (QG ≥ QG,N). Important conclusion is that corresponding potier reactance values practically equally that in rated regime. It is enabled that excitation current calculations and construction corresponding generator capability curves (P-Q curve) performed by potier reactance rated values (xp≈xpN) and the open-circuit saturation curve. From reactive load test are dermined xp,N values. Greatest difference between P-Q curves, obtained from designers and by presented procedure, is result change of generator voltage in relation to rated. It is shown that P-q curve calculation in high reactive power region by Potir method is simple and sufficiently accurate.

Keywords

References

*** (2012) Konstrisanje stvarnih pogonskih dijagrama generatora (P-Q krive generatora) po novoj metodi za određivanje Potjeove reaktanse) - studija. Beograd: Elektrotehnički institut Nikola Tesla, str. 12
Adibi, M.M., Milanicz, D.P. (1994) Reactive capability limitation of synchronous machines. IEEE Transactions on Power Systems, 9(1): 29-40
Boldea, I. (2006) Synchronous generators. Boca Raton, FL: CRC Press
Chari, M.V.K., Csendes, Z.J., Minnich, S.H. (1981) Load characteristics of synchronous generators by the finite-element method. IEEE Transc. on Power Apparatus and Systems, vol.PAS-100, br. 1, Jan, str. 1-13
El-Serafi, A.M., Wu, J. (1991) A new method for determining the armature leakage reactance of synchronous machines. IEEE Transactions on Energy Conversion, 6(1): 120
Fitzgerald, A.E., Kingsley, C. (1962) Električne mašine za naizmeničnu i za jednosmernu struju. Beograd: Naučna knjiga
Kostić, M.M. (2014) Determining the generator potier reactance for relevant (reactive) loads. Elektrotehniški vestnik, English edition, Vol. 79(3), pp. 31-36
Kostić, M. (2009) Nova metoda za određivanje Potjeove reaktanse sinhronih turbogeneratora. Elektroprivreda, vol. 62, br. 4, str. 8-17
Kostić, M.M. (2015) Doprinos proračunu i analizi zavisnosti između reaktanse rasipanja i Potjeove reaktanse sinhronih generatora. Tehnika, vol. 70, br. 4, str. 647-654
Nilsson, N.E., Mersurio, J. (1994) Synchronous generator capability curve testing and evaluation. IEEE Transactions on Power Delivery, 9(1): 414