Sažetak

(ne postoji na srpskom)
A method to measure ground impedance in various soil structures is described, which takes into account inductive coupling between current and potential wires. For this purpose, a family of coupling effect curves versus the potential wire length was calculated. It was found that these curves are not dependent on the current wire length and are practically identical to the same soil resistivity. The true resistance of the substation grounding is determined using received coupling effect curves, and a simple formula which subtracts the coupling effect from the measured substation grounding resistance. Practical comparative measurements were performed to validate the method.

Ključne reči

coupling effect; ground impedance; impedance measurement; soil resistivity; substation

Reference

*** (1991) IEEE Standard 81.2-1991: IEEE guide for measurement of impedance and safety characteristics of large, extended or interconnected grounding systems. NY, USA, Jan
Biddle, J.G. (1970) Manual on Ground Resistance Testing. Philadelphia, PA: USA
Carson, J.R. (1927) Wave propagation in overhead wires with ground return. Bell System Technical Journal, str. 539-554, Oct
Deri, A., Tevan, G., Semlyen, A., Castanheira, A. (1981) The Complex Ground Return Plane Simplified Model for Homogeneous and Multi-layer Earth Return. IEEE Transactions on Power Apparatus and Systems, PAS-100, 8, 3686-3693
Farber, A., Katz, B. (2009) Israel electric validates earthing measurements. Transmission and Distribution World, vol. 61, br. 7, July str. 52-56
Foster, R.M. (1931) Mutual Impedance of Grounded Wires Lying on the Surface of the Earth. Bell System Technical Journal, 10, 3, 408-419
IEEE (2000) IEEE guide for safety in AC substation grounding. ANSI/IEEE Std. 80/2000
Ma, J., Dawalibi, F.P. (2001) Influence of Inductive Coupling between Leads on Ground Impedance Measurements using the Fall-of-potential Method. IEEE Transactions on Power Delivery, 16 (4): 739-743
Rogers, E.J., White, J.F. (1989) Mutual Coupling between Finite Lengths of Parallel or Angled Horizontal Earth Return Conductors. IEEE Transactions on Power Delivery, 4 (1): 103-113
Sarmiento, H.G., Reynolds, P.H., Mukhedkar, D. (1988) An Extension to the Study of Earth-return Mutual Coupling Effect in Ground Impedance Field Measurements. IEEE Transactions on Power Delivery, 3 (1): 96-101
Tagg, G.F. (1964) Measurement of earth-electrode resistance with particular reference to earth-electrode systems covering a large area. Proceedings of the Institution of Electrical Engineers, 111(12): 2118