Analiza rada diferencijalne zaštite transformatora pri pojavi zasićenja strujnih mernih transformatora - softverske simulacije i ispitivanja
Analysis of operation of transformer differential protection under current transformer saturation: Software simulations and relay testing
aUniverzitet u Beogradu, Elektrotehnički institut 'Nikola Tesla', Srbija bUniverzitet u Beogradu, Elektrotehnički fakultet, Srbija
e-adresa: nikola.sucevic@ieent.org
Ključne reči: zasićenje strujnih mernih transformatora za zaštitu; diferencijalna zaštita transformatora; softverske simulacije; ispitivanje zaštitnih uređaja
Keywords: current transformer saturation; transformer differential protection; software simulations; relay testing
Sažetak
U ovom radu analiziran je uticaj pojave zasićenja strujnih transformatora, usled struja kvarova velikih vrednosti u sistemu, na talasni oblik struje na sekundaru strujnih transformatora, kao i analiza rada diferencijalne zaštite transformatora u takvim uslovima. Analize su vršene na softverskom modelu zaštitnog uređaja, a potom i na stvarnom uređaju injektiranjem odgovarajućih signala na njegove ulaze, primenom ispitnog kofera za ispitivanje zaštitnih uređaja. Potom je izvršena komparacija odziva softverskog modela i stvarnog uređaja. Modelovanje mreže i analize vršene su u softverskom paketu DlgSILENT PowerFactory, a ispitivanja zaštitnog uređaja su vršena pomoću DOBLE ispitnog kofera.
Abstract
In the paper the analyses of the current transformer saturation influence to operation of differential protection are presented. Analyses are performed using a simulation tool and a relay model, as well as using the physical relay by injecting test currents from test equipment on relay inputs. The comparison of relay behavior in these two analyses has been performed and discussed. Network modeling has been performed in DIgSILENT PowerFactory and physical relay testing using DOBLE test equipment.
|
|
|
Reference
|
|
*** (2016) SIPROTEC 4: 7UT6x: Manual C53000-G1176-C230-5. Edition 09
|
|
*** DIGSI 4: Operation Software for SIPROTEC 4, SIPROTEC Compact, SIPROTEC 3 and SIPROTEC 2 protection devices
|
|
*** Theory for CT SAT Calculator (PSRC): Spreadsheet originated by the IEEE PSRC committee responsible for C37.110: IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes
|
|
*** Transformer Differential Protection: SIPROTEC 4 7UT6 differential protection relay for transformers, generators, motors and busbars. u: Siemens SIP, Edition No. 7
|
|
Bertrand, P., Mendik, M.M., Hazel, T., Tantin, P. (2009) CT saturation calculations: Are they applicable in the modern world? CT sizing as per IEC standards and the benefits of non conventional instrument transformers. u: 2009 Record of Conference Papers: Industry Applications Society Annual: Petruleum and Chemical Industry Conference (56th): PCIC, IEEE, part IV
|
|
Blackburn, J.L. (1987) Protective Relaying: Principles and Applications. New York: Marcel Decker, Inc
|
|
Cosse, R.E., Dunn, D.G., Spiewak, R.M., Zocholl, S.E., Hazel, T., Rollay, D.T. (2007) CT Saturation Calculations: Are They Applicable in the Modern World? Proposed Responsibilities. u: Petroleum and Chemical Industry Technical Conference: PCIC '07, IEEE, Part II
|
|
Cosse, R.E., Dunn, D.G., Spiewak, R.M. (2005) CT Saturation Calculations: Are They Applicable in the Modern World? The Question. u: Record of Conference Papers Industry Applications Society Annual Petroleum and Chemical Industry Conference (52nd), IEEE, Part I
|
|
Cosse, R.E., Dunn, D.G., Spiewak, R.M., Bowen, J.E. (2008) CT saturation calculations: Are they applicable in the modern world? Low-ratio, high-current CT/microprocessor relay comparisons at a high-current testing laboratory. u: 2008 55th IEEE Petroleum and Chemical Industry Technical Conference (55th): PCIC, IEEE, Part III
|
|
DIgSILENT PowerFactory (2017) Current Transformer (StaCT): Technical Reference Documentation
|
|
DIgSILENT PowerFactory (2017) Two-Winding Transformers (ElmTR2, TypTr2): Technical Reference Documentation
|
|
DIgSILENT PowerFactory Relay Model Description: Siemens 7UT6xx. Version 002, Technical Reference Documentation
|
|
Doble Engineering Company https://www.doble.com
|
|
Doble Engineering Company TransWin 3.3: User's Guide
|
|
Hargrave, A., Thompson, M.J., Heilman, B. (2018) Beyond the knee point: A practical guide to CT saturation. u: Annual Georgia Tech Protective Relaying Conference (72nd), Atlanta, Georgia
|
|
IEEE Power Engineering Society (2007) IEEE Standard requirements for Instrumental Transformers. C57.13
|
|
IEEE Power Engineering Society (2007) IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes. C37.110
|
|
International Electrotechnical Commission Instrument transformers: Requirements for protective current transformers for transient performance. Part 6: IEC 60044-6
|
|
International Electrotechnical Commission Instrument transformers: Current transformers. Part 1: IEC 60044-1
|
|
Kasztenny, B., Mazereeuw, J., Docarmo, H. (2007) CT Saturation in Industrial Applications: Analysis and Application Guidelines. u: 2007 Annual Conference for Protective Relay Engineers (60th), March 27-29, IEEE
|
|
Schneider Electric Current transformers: Specification errors and solutions. Cahier technique no. 195, http://www.schneider-electric.com
|
|
|
|